Q1 Flame Retardant
- REACH
- RoHS
- CE
- CPR Compliant
Lead & Mercury Free | Flame Retardant | Super Flexible & Safe
Application
Q1 FR is ideal for wiring in spaces where high flexibility and safe performance are essential. Suitable for powering lighting circuits, switches, and electrical outlets, it is designed to meet everyday wiring needs with flame-retardant insulation and eco-conscious construction
Technical Data
Approvals: IS 694 marked, FIA/TAC
Voltage Grade: Up to and including 1100 V
Conductor: Thin strands of electrolytic copper are multi-drawn for uniformity of resistance, dimension and flexibility.
Insulation: Specially formulated FR (Flame Retardant) PVC insulation with anti rodent and anti termite properties.
Insulation Conformity: IS 5831, Type D FR 70° C.
Colours: Red, yellow, blue, black, green, grey & white
Marking: The cables are printed with marking of ‘Q1 FR’.
Packing: 90 meter coil is packed in protective cartons.
Properties
- Self extinguishing and Flame Retardant
- Temperature Range: -15° C to +70° C
- Excellent flexibility and ease of installation
- Anti-Rodent & Anti-Termite
- 100% Electrolytic Grade Pure Copper
- Lead and Mercury Free
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – grey, 07 – white.
| Part Number | **Nominal Cross Sectional Area (sq. mm) | Number/Max. Dia. of Strands | Nominal / Insulation Thickness (mm) | Approx. Overal Diameter (mm) | Max.DC Conductor Resistance at 20°C (Ω/km) | *Current Rating (Amps) | |
| Casing | Concealed | ||||||
| 01210102xx20 | 0.75 | 24/0.21 | 0.6 | 2.3 | 26.0 | 9 | 8 |
| 01210103xx20 | 1 | 32/0.21 | 0.6 | 2.6 | 19.5 | 12 | 11 |
| 01210104xx20 | 1.5 | 30/0.26 | 0.6 | 2.8 | 13.3 | 16 | 15 |
| 01210105xx20 | 2.5 | 50/0.26 | 0.7 | 3.4 | 7.98 | 23 | 19 |
| 01210106xx20 | 4.0 | 56/0.31 | 0.8 | 4.1 | 4.95 | 30 | 26 |
| 01210107xx20 | 6.0 | 84/0.31 | 0.8 | 4.6 | 3.30 | 38 | 33 |
- * As per IS 3961 (Part V)
- ** As per conductor class 5 of IS 8130
Test Parameters for assessment of FR properties
| Test | Test Method | Values |
| Limited Oxygen Index | IS 10810 P-58 | > 29% |
| Limited Temp. Index | IS 10810 P-64 | > 250 °C |
*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)